Error E1 / EL01 on Midea, Vivax and Inventor splits – what it means and what to check
Roman Oškrobaný · · 3 min read
E1 or EL01 on the indoor unit's display is one of the most common codes on Midea splits. It means a communication error between the indoor and the outdoor unit: the indoor unit sends messages but gets no answer from the outdoor unit. You will see the same code with the same meaning on Vivax and Inventor units made by Midea. But watch out for one exception – more on it below.
E1 or EL01?
Midea uses two code systems:
Older units (about 2017–2019) show a 2-character code: E1.
Current units show a 4-character code: EL01, sometimes with a space (EL 01). The second letter L means "other" – it is not a fault of the indoor unit (H) or the outdoor unit (C) on its own, but of the link between them.
Units without a display show it with the lamps: the run lamp blinks twice and the timer lamp is off.
Both codes mean the same. Which one you see depends on the display board, not on the fault.
Where you see E1 / EL01
Unit
Code
Meaning
Midea Oasis Plus, All Easy Pro, Breezeless, Xtreme Save (R32, current)
EL01
communication
Midea Oasis Plus 2018
E1
communication
Vivax AERI PRO, AEMI PRO, AEQI PRO and other PRO models
EL01
communication
Vivax AEYIs
E1
communication
Vivax AENI, AEHI+
E1 or EL01, depending on the display
communication
Inventor Aria AR5
E1 or EL01, depending on the display board
communication
Inventor Leon
EL01
communication
Inventor U6RSL (multi-split)
E1 or EL01
communication
Vivax T Design (ACP-…LCTI)
E1
room temperature sensor – a different maker
Vivax T Design is not made by Midea. Its E1 means a fault of the indoor unit's room temperature sensor, not communication.
From the Midea and Inventor service manuals, roughly from the most common:
The interconnecting cable and terminals: wires in the wrong order, a loose or corroded terminal, a damaged cable, a joined cable.
The outdoor board's supply or the IPM board: the 5 V and 12 V supplies are missing.
A shorted load on the outdoor board, for example the coil of the electronic expansion valve (EEV).
The reactor (on some models): open circuit.
The indoor or outdoor control board.
The board is last on the list on purpose: most E1 / EL01 faults turn out to be the cable and the terminals.
What to check, in this order
Switch the power off and on again. If the code goes away and doesn't come back, it may have been a one-off disturbance. If it comes back, carry on.
The interconnection and terminals at both units: wires in the order of the wiring diagram, terminals tight, no corrosion, the cable undamaged and not joined.
Measure the DC voltage between terminals S and N (on current units, terminals 2 and 3 of the outdoor unit). With working communication the reading swings – on current units by about ±25 V. Steadily positive → look on the outdoor unit's side; steady (or about 0 V) → on the indoor unit's side.
The outdoor board's supply: the 5 V and 12 V voltages.
Disconnect the loads on the outdoor board one at a time (for example the EEV coil) – if the code goes away when one is disconnected, you have found the short.
The reactor, if the model has one: about 0 Ω.
The control board last of all.
On a multi-split, first find out whether every indoor unit shows the code. If they all do, the fault is almost certainly on the outdoor unit's side. On Inventor U6RSL multi-splits the outdoor unit's data check shows how many indoor units the outdoor unit can see.
In the ClimaToolkit app you can look the code up by the model number on the nameplate in error codes: the app picks the right code table and shows the causes and checks for that series.