The F-gas label at commissioning – what to write on it and how to work it out

Roman Oškrobaný · · 5 min read

Illustration: a label reading F-gas

Every air conditioner and heat pump with an F-gas carries a label. The maker writes on it what was charged in the factory. With a split, though, refrigerant is often added only on site – and then two numbers that the technician writes in belong on the label: how much refrigerant was added and what the total charge is. They must be there before you start the unit. This post covers what the label must show, how to work out those two numbers, and why they are more than a formality.

What is on the label

Since 1 January 2025 every piece of equipment with F-gases carries a label under Article 12 of Regulation (EU) 2024/573. It states:

  • that the equipment contains fluorinated greenhouse gases,
  • the gas designation, for example R-32,
  • the quantity in kg and in tonnes of CO₂ equivalent,
  • the global warming potential (GWP),
  • "hermetically sealed", where that applies.

The label must be legible and permanent, next to the service ports or on the part that holds the gas, and in the language of the country where the equipment is sold – Slovak in Slovakia, Czech in Czechia. The same information is in the manual.

Implementing Regulation (EU) 2024/2174 sets the label's format. Where refrigerant can be added on site, the label has room for the added amount and for the total charge, and the installer fills them in before putting the equipment into operation.

How to work out the added amount

The outdoor unit's factory charge is enough for a certain pipe length. The installation manual gives two numbers: the length the factory charge covers and how many grams of refrigerant to add for each extra metre.

  • Added = (pipe length − pre-charged length) × grams per metre. Or what you actually weighed in, if you charged by the scale.
  • Total charge = factory charge + added.
  • t CO₂-eq = total charge in kg × GWP ÷ 1,000.

If the pipe is shorter than the factory charge covers, nothing is added: added is 0 kg and the total charge equals the factory charge. On a multi-split all circuits are added up: the length of all pipes together and one added amount for the whole unit.

Example (made-up numbers; the real ones are in the installation manual)
ItemValue
RefrigerantR32, GWP 675
Factory charge1.00 kg
Pre-charged length7 m
Add per extra metre20 g/m
Pipe length12 m
Added(12 m − 7 m) × 20 g/m = 100 g = 0.10 kg
Total charge1.00 kg + 0.10 kg = 1.10 kg
t CO₂-eq1.10 × 675 ÷ 1,000 = 0.74 t

Grams per metre differ by maker, model and liquid pipe size. Always take them from the manual for that unit.

Why these numbers matter

  • The 3 kg limit and the A1 or A2 certificate. An A2 certificate covers charges under 3 kg only. What counts is the total charge, including the refrigerant added on site. If the total charge is 3 kg or more, only a technician with an A1 certificate may commission the unit.
  • The 5 t CO₂-eq limit. From there on, regular leak checks and the equipment record are required. For R32 that is about 7.4 kg, so most splits are below it. For R410A it is already about 2.4 kg. R454B gets there sooner through its R1234yf: 1 kg of it (from about 3.2 kg of R454B) counts on its own.
  • One number everywhere. The added amount is shown separately in the equipment record, and in Slovakia the company also reports it in the yearly report due by 31 January. Work it out once, at installation, write the same number on the label and in the record, and they will never differ.
  • Later service. Whoever repairs the unit or recovers its refrigerant in five years will see on the label how much should be in it. Without the added amount they see only the factory charge, which no longer holds.
Where the limits fall
RefrigerantGWP (EU)5 t CO₂-eq
R326757.41 kg
R454B≈ 46510.75 kg
R410A≈ 2,0882.40 kg

kg × GWP ÷ 1,000. R454B is 31 % R1234yf, which counts on its own from 1 kg: its leak checks start at about 3.22 kg. GWP from Annexes I and VI of Regulation 2024/573 (for R32, 675; the 771 you sometimes see is a newer value the law does not use).

When and how to fill it in

  1. The pipework is finished, the pressure test and the vacuum are done.
  2. Measure the pipe length (on a multi-split, all circuits) and find the pre-charged length and grams per metre in the manual.
  3. Add the refrigerant – preferably by weight – and write down how much you really added.
  4. Before start-up, write the added amount and the total charge on the label with a permanent marker.
  5. Write the same numbers in the commissioning record.

In the ClimaToolkit app, under Commissioning on a unit's page in Units and F-gas, the "On the F-gas label" box works this out: from the pipe length, the pre-charged length and grams per metre it shows how much to add, compares it with what you added, and shows the total charge and the t CO₂-eq. The same numbers then go into the equipment record and the PDF.

Try it in the app

  • Units and F-gasPart of Pro (during the beta, free for everyone who signs in)

Sources

  1. Regulation (EU) 2024/573 on fluorinated greenhouse gases, Art. 5, 7 and 12, Annexes I and VI. EUR-Lex (opens in a new tab)
  2. Implementing Regulation (EU) 2024/2174 (labels), Art. 1(5). EUR-Lex (opens in a new tab)
  3. Implementing Regulation (EU) 2024/2215 (A1 and A2 certificates). EUR-Lex (opens in a new tab)
  4. Slovakia: Act 286/2009 Coll. on fluorinated greenhouse gases, § 5a (in Slovak). Slov-Lex (opens in a new tab)
  5. Slovakia: Decree 314/2009 Coll., § 2(4) (the sticker after a leak check; in Slovak). Slov-Lex (opens in a new tab)