R32 vs R410A – what really changes for the technician

Roman Oškrobaný · · 4 min read

Illustration: the refrigerants R32 and R410A

R410A filled splits and heat pumps for about twenty years. Today almost every new split holds R32. On the gauges they look alike, but more changes for the technician than you might think: a different safety class, different limits for leak checks and different EU ban dates. This post compares what matters on the job.

At a glance

R32 and R410A side by side
R32R410A
Make-upsingle substance (CH₂F₂)blend of R32 / R125, 50 / 50 %
Glide0 K≈ 0.1 K
Safety classA2L – mildly flammableA1 – no flame spread
GWP in EU law675≈ 2,088
Pressure at 0 °C7.1 bar g7.0 bar g
Pressure at 40 °C23.8 bar g23.2 bar g
OilPOE · PVEPOE · PVE
Leak checks from (5 t CO₂-eq)7.41 kg2.40 kg

Gauge pressures at sea level. GWP from Annexes I and VI of Regulation 2024/573; the newer values (R32 771, R410A 2,256) are not used by the law.

The pressures are very close – on the gauges you can hardly tell them apart. The difference lies elsewhere.

Flammability: A2L

R32 is mildly flammable (A2L): such gases burn at no more than 10 cm/s, R32 at about 6.7 cm/s. For the work that means:

  • no open flame or sparks near a leak;
  • a leak detector and a recovery machine rated for A2L;
  • a vacuum pump with a non-return valve, which Daikin says to keep for R32 only;
  • before brazing, recover or isolate the refrigerant and purge with nitrogen before and during brazing;
  • never pump down a leaking circuit with the unit's own compressor – the air it draws in can make the compressor explode; use a recovery machine;
  • when an HFC burns, it gives off toxic hydrogen fluoride – another reason to keep flames away from a leak.

How much R32 a room may hold depends on the floor area and the height the unit is mounted at (IEC 60335-2-40). For a wall unit up to about 1.2 kg there is no minimum area; with larger charges, typically on multi-splits, check it in the unit's manual – and count the whole charge of the circuit.

Charging and service

  • R32 is a single substance: one pressure–temperature table, no glide, and after a leak it can be topped up without changing its make-up.
  • R410A is a blend with a small glide (about 0.1 K) and behaves almost like a single substance. It is still charged as liquid.
  • A unit is built for one refrigerant. Charge only the refrigerant on the nameplate and never mix refrigerants.

The pressure–temperature calculator gives the saturation pressure and temperature of both.

Leak checks

Mandatory leak checks and the equipment record start at 5 t CO₂ equivalent. For R32 that is 7.41 kg – more than any ordinary split holds. For R410A it is 2.40 kg, so a larger split or a multi-split with R410A can be above the limit. Which unit needs checks, and when, is worked out in Units and F-gas.

EU bans

What stops being sold, and when (new equipment)
FromWhatAffects
1 Jan 2025single splits under 3 kg with GWP 750 or morenew splits with R410A
1 Jan 2029air-to-air splits up to 12 kW with GWP 150 or morenew splits with R32 (and R454B)
1 Jan 2035splits up to 12 kW with any F-gasall F-gases

Equipment placed on the market before a ban date may still be installed. Most bans have an exception where on-site safety rules don't allow the lower-GWP option.

Servicing stays allowed for both. The servicing ban for air conditioners and heat pumps from 1 January 2026 covers gases with GWP 2,500 or more – R410A (≈ 2,088) and R32 (675) are both below it. But HFC supply to the EU market falls step by step to zero in 2050, so both refrigerants will get scarcer and dearer.

So?

  • A new split today means R32 – new single splits with R410A under 3 kg may not be placed on the market since 2025.
  • Existing R410A units can still be serviced and topped up; just mind the 2.40 kg leak-check limit.
  • With R32 the pressures are almost the same, but you need A2L-rated tools, no flame near a leak, and a room-size check for larger charges.
  • And note 2029: that is when the ban reaches new R32 splits too.

Try it in the app

Sources

  1. Regulation (EU) 2024/573 on fluorinated greenhouse gases, Annexes I, IV, VI and VII. EUR-Lex (opens in a new tab)
  2. BITZER, Refrigerant Report, refrigerant tables.
  3. CoolProp, saturation data for R32 and R410A.
  4. Chemours, Freon 410A product information.
  5. Solstice Advanced Materials, Genetron AZ-20 (R-410A).
  6. ANSI/ASHRAE, Addendum ak to Standard 34-2007 (2010): subclass 2L.
  7. Daikin, Adopting R-32 VRV technology: a practical guide to the safety standards (ECPEN26-228).
  8. Daikin, R32 2MXM installation manual and installer reference guide (2026).
  9. Midea, R32 (R290) safety manual, Breezeless E documentation.
  10. Fujitsu General, ABEG30KRTA (R32) installation manual, p. En-1.