Inventor error codes

Inventor's wall units and multi splits use Midea-built control boards, so most codes match Midea's. The Aria AR5 shows either the short or the long code depending on its display board; the Leon shows long codes only. Codes for the Emperor range are not confirmed yet.

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5

The codes of the Inventor Aria AR5 wall-mounted split (AR5VI / AR5VO, sizes 09–24), from Inventor's service manual. The unit is Midea-built and uses Midea's codes: depending on the display board it shows the short 2-character code or the long 4-character one.

How to read codes on this unit
  • The display shows either the short code (E1) or the long code (EL01), depending on the display board. Each code below lists its long form as the other spelling.
  • Units without a display flash the lamps instead: the operation lamp blinks a number of times, and the timer lamp is off, on or flashing.
  • Information inquiry (live readings): within 10 s press LED (Do Not Disturb) ×3, then SWING (Air Direction) ×3. LED shows the next item, SWING the previous one.
  • Items: T1, T2, T2B, T3, T4, TP, TH, FT, Fr, IF, OF, LA, CT, ST. Frequencies of 100 Hz and more start with a letter: A0–A9 = 100–109 Hz, b = 110s … F = 150s. LA is a hex value; ×2 = EXV opening in pulses. The manual does not say what the ST values mean.
  • Outdoor board LEDs: some outdoor units have a red and a green LED on the board (see below).
  • Garbled code: if the unit still obeys the remote, suspect the display board; if not, the indoor PCB.

Display codes

The lamp patterns are from the manual's short-code table. The lamp patterns of the long-code display could not be read from the manual, and Midea's own lamp patterns for the long codes are different: on an AR5 that shows long codes, confirm on the unit before relying on the lamps.

Inventor – Leon (LHUVI / LEUVI)

Ranges
  • Leon

The codes of the Inventor Leon wall-mounted splits (LHUVI / LHUVO and LEUVI / LEUVO, sizes 09–24), from Inventor's service manual. The unit is Midea-built: the display shows Midea's 4-character codes, and engineer mode shows a longer list.

How to read codes on this unit
  • The indoor display shows long 4-character codes only (EL01). The lamps flash too, but the lamp column of the manual's table could not be read reliably, so no lamp patterns are given here.
  • Engineer mode: with the unit on or in standby and the remote unlocked, hold ON/OFF + FAN for 7 s. ▲ / ▼ scroll through items 0–30: the current error code, then T1, T2, T3, T4, TP, FT, Fr, dL, Uo, Sn, Pr (×8), Lr (×8), ir (×8), Hu, TT, oT. Exit with ON/OFF + FAN for 2 s, or wait 60 s. Which item number belongs to which reading is not confirmed.
  • Outdoor board LED: PC02, PC04, PC08, PC40 and PC03 are shown as 1, 3, 5, 6 and 7 flashes, but which code takes which count could not be read from the manual. Read the code on the indoor display instead.
  • Not errors: dF (defrost), SC, CL (active clean), FP (8 °C heating), FC (forced cooling), AP (Wi-Fi AP mode), CP (remote switched off).

Display codes

The causes and checks come from Midea's EX R32 service manual (the same code family). The Leon manual's own troubleshooting charts are on L1 95–121.

Engineer-mode codes

Shown only by the error-code item in engineer mode. The manual's text was shifted by one row; the list was put back in order and matches Midea's extended list except where noted.

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Codes from the Inventor multi split service manual for the U6RSL(2)-18, U6RSL(3)-27 and U6RSL(5)-42 outdoor units and the indoor units connected to them. The 2-port (2)-18 shows 2-character codes on its outdoor display; the (3)-27 and (5)-42 show 4-character codes for the same faults.

How to read codes on this unit
  • Indoor units show the indoor codes on their display. Units without a display flash the lamps instead: the operation lamp blinks a number of times, and the timer lamp is off, on or flashing (2 Hz).
  • Outdoor 7-segment display: -- = standby; a number = running frequency in Hz; dF = defrost; PH = pre-heat; RO = oil return; LC = low-ambient cooling; FC = forced cooling; E6 = 3 PFC trips within 15 min; CE = auto-correction running. Anything else is an error code.
  • Outdoor codes clear at least 30 s after the fault has gone, except E2 and E3 on the (2)-18.
  • Point check (SW1): press SW1 repeatedly while the unit runs to step through the readings. On the (3)-27, press 49 shows why the unit stopped; on the others, press 45 shows the last error code (00 = none) and press 52 the reason for the last shutdown.
  • Wiring / piping auto-correction: hold the outdoor check switch for 5 s until CE shows; it takes 5–10 min.
  • The U5MRSL (4-port) and the Midea M2OH / M3OE outdoor units are covered only by inference from this manual: the U5MRSL is the same Inventor multi range without its own service manual; for the M2OH / M3OE the hints are the shared GMCC compressor and the Midea outdoor model names in this manual. Check the 7-segment display on the unit before relying on this table for them.

Indoor unit codes

Shown on the display or by the lamps of the indoor units connected to the multi.

Outdoor display codes: U6RSL(2)-18

The 2-character codes on the 7-segment display of the 2-port outdoor unit.

Outdoor display codes: U6RSL(3)-27 and U6RSL(5)-42

The 4-character codes on the 7-segment display of the 3-port and 5-port outdoor units.