Inventor error codes

Display codes

Inventor EC

Refrigerant leak detected

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5
  • Indoor unit
  • Also shown as EL0C
  • Lamps: run lamp blinks 7×, timer lamp off

Likely causes

Leak, blockage, coil sensor T2 loose, indoor PCB.

First checks

Is cold air coming out? → leak test, repair and recharge; check for a blockage; check that T2 sits firmly on the coil → indoor PCB last.

Note

Set when T2 does not drop by at least 1 °C in the first 5 min of running at 50 Hz or less, three times.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.062022, ManualsLib page 107

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi
  • Lamps: run lamp blinks 7×, timer lamp off

Likely causes

Leak, blockage, coil sensor T2 not attached to the coil.

First checks

Is cold air coming out? → check that T2 sits on the coil → search for a leak; check for a blockage.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31, 42–43