Inventor EC54

Discharge sensor TP open or short

Inventor – Leon (LHUVI / LEUVI)

Ranges
  • Leon
  • Outdoor unit

Likely causes

Sensor, its connector, outdoor PCB.

First checks

Check the connector; measure the sensor's resistance against its table (TP ≈ 54.9 kΩ at 25 °C) → out of range: replace the sensor, else the PCB.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.072023, ManualsLib page 81–82

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Discharge sensor T5 open or short

Likely causes

Sensor, its connector, outdoor PCB.

First checks

Check the connector → measure the sensor's resistance against its R-T table (5 kΩ at 90 °C) → replace the sensor or the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 33–34