Inventor error codes

Display codes

Inventor EL01

Indoor ↔ outdoor communication error

Inventor – Leon (LHUVI / LEUVI)

Ranges
  • Leon
  • Indoor unit

Likely causes

Interconnect wiring, outdoor PCB or IPM-board supply, a shorted load, EEV coil, indoor PCB.

First checks

Power-cycle; check the wiring and terminals; measure DC volts between outdoor terminals 2 (S) and 3 (N): it should swing about ±25 V; always + → outdoor side, fixed → indoor side; check the 5 V and 12 V supplies; unplug the loads one by one.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.072023, ManualsLib page 81–82

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Likely causes

Interconnect wiring, IPM board or main board, indoor PCB.

First checks

Do all indoor units show it? → measure the DC voltage between S and N: it should swing between + and − → check the LEDs on the IPM board and the main board → check the reactor; point check press 1 shows how many indoor units the outdoor unit sees.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 36–38