Inventor error codes

Display codes

Inventor P0

IPM malfunction or IGBT over-current

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5
  • Outdoor unit
  • Also shown as PC00
  • Lamps: run lamp blinks 1×, timer lamp flashing

Likely causes

Compressor wiring, poor ventilation, compressor, IPM.

First checks

Check the compressor wiring → outdoor fan and ventilation → compressor windings → IPM continuity (P to U, V, W, N and U, V, W to N: several MΩ) → outdoor PCB.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.062022, ManualsLib page 109

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

IPM module protection

  • Lamps: run lamp blinks 1×, timer lamp flashing

Likely causes

Supply, wiring, compressor, outdoor fan, bridge rectifier, PFC.

First checks

Measure the DC voltage P–N → check the supply → the wiring between the main board and the IPM → the compressor leads → the IPM → the outdoor fan → the bridge rectifier → the reactor → the PFC → the compressor.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31, 53

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Compressor top temperature protection

Likely causes

Poor airflow, refrigerant circuit, compressor overload protector (OLP).

First checks

Wait 10 min → is the top of the compressor above 90 °C? → the OLP should read 0 Ω → check the refrigerant circuit → replace the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 54

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.