Inventor error codes

Display codes

Inventor P2

IPM high temperature or high pressure

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5
  • Outdoor unit
  • Also shown as PC02
  • Lamps: run lamp blinks 3×, timer lamp flashing

Likely causes

Poor contact between IPM and heatsink, poor airflow, outdoor PCB.

First checks

Tighten the heatsink screws and renew the thermal grease → replace the outdoor PCB.

Note

On units with a high-pressure switch, the switch opens above 4.4 MPa.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.062022, ManualsLib page 111

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.

Open in the appAll Inventor error codes