Inventor error codes

Display codes

Inventor P5

Indoor units in conflicting modes (multi split)

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5
  • Indoor unit
  • Also shown as --
  • Lamps: run lamp blinks 6×, timer lamp flashing

Likely causes

Rooms set to heating and cooling at the same time.

First checks

Set all rooms to modes that work together.

Note

Only with a multi-split outdoor unit.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.062022, ManualsLib page 85

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Condenser high-temperature protection (T3 above 65 °C)

Likely causes

Outdoor ambient above 50 °C, poor ventilation, outdoor fan, dirty outdoor coil, low refrigerant charge.

First checks

Check the outdoor temperature → the space and airflow around the unit → the outdoor fan → clean the coil → check the charge.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 52