Inventor error codes

Display codes

Inventor P6

Low-pressure protection

Inventor – Aria AR5 (AR5VI / AR5VO)

Ranges
  • Aria AR5
  • Outdoor unit
  • Also shown as PC03
  • Lamps: run lamp blinks 7×, timer lamp flashing

Likely causes

Wiring, low-pressure switch, refrigerant circuit, PCB.

Note

The low-pressure switch opens below 0.13 MPa. Only on some models.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.062022, ManualsLib page 114

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi
  • Lamps: run lamp blinks 7×, timer lamp flashing

Likely causes

Closed service valve, low refrigerant charge, low-pressure switch.

First checks

Check that the service valves are open → check the charge → check the low-pressure switch.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

IPM module protection

Likely causes

Supply, wiring, compressor, outdoor fan, bridge rectifier, PFC.

First checks

Measure the DC voltage P–N → check the supply → the wiring between the main board and the IPM → the compressor leads → the IPM → the outdoor fan → the bridge rectifier → the reactor → the PFC → the compressor.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 53

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.