Inventor error codes

Display codes

Inventor PC02

Compressor-top or IPM over-temperature, or high pressure

Inventor – Leon (LHUVI / LEUVI)

Ranges
  • Leon
  • Outdoor unit

Likely causes

Blocked airflow, low charge or a blockage, poor heatsink contact, overload protector.

First checks

Check the airflow; wait 10 min; compressor top above 90 °C → check the refrigerant circuit; tighten the heatsink screws and renew the thermal grease; overload protector should read 0 Ω.

Source: Inventor Wall Mounted Unit Service Manual V:1.0.072023, ManualsLib page 81–82

Inventor U6RSL multi split (Midea-built)

Ranges
  • U6RSL multi
  • U5MRSL multi

Compressor top temperature protection

Likely causes

Poor airflow, refrigerant circuit, compressor overload protector (OLP).

First checks

Wait 10 min → is the top of the compressor above 90 °C? → the OLP should read 0 Ω → check the refrigerant circuit → replace the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 54