Midea error codes

Indoor unit codes

Midea E1

Indoor ↔ outdoor communication error

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi
  • Lamps: run lamp blinks 2×, timer lamp off

Likely causes

Interconnect wiring, outdoor IPM board or main board, indoor PCB.

First checks

Do all indoor units show it? → measure the DC voltage between S and N: it should swing between + and − → check the LEDs on the IPM board and the main board → check the reactor; outdoor point check press 1 shows how many indoor units the outdoor unit sees.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31, 36–38

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018
  • Indoor unit
  • Lamps: run lamp blinks 2×, timer lamp off

Likely causes

Interconnect wiring, reactor, outdoor PCB, indoor PCB.

First checks

Check the wiring and terminals; measure DC volts between outdoor terminals 2 and 3: the reading should swing between + and −; always + → outdoor side, fixed → indoor side; reactor ≈ 0 Ω.

Note

Shown when the indoor unit gets no reply for 150 s, four times while running.

Source: Oasis Plus 3D Inverter Series 2018 Service Manual, R32, p. 62–63

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.