Midea error codes

Indoor unit codes

Midea E3

Indoor fan speed out of range

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi
  • Lamps: run lamp blinks 4×, timer lamp off

Likely causes

Fan motor, indoor PCB.

First checks

Turn the fan by hand → check the voltages at the motor connector → replace the motor or the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

IPM board ↔ main board communication error

Likely causes

Signal wire, IPM board, main board.

First checks

Is any LED on the IPM board lit? → check the signal wire → replace the IPM board → replace the main board.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 45

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018
  • Indoor unit
  • Lamps: run lamp blinks 4×, timer lamp off

Likely causes

Fan motor, its wiring, indoor PCB.

First checks

Turn the fan by hand (seized?) → check the motor connector and its voltages → replace the motor or the PCB.

Note

Out of range = below 300 or above 1500 rpm.

Source: Oasis Plus 3D Inverter Series 2018 Service Manual, R32, p. 64–65

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.

Open in the appAll Midea error codes