Midea error codes

Indoor unit codes

Midea E5

Indoor coil sensor T2 open or short

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi
  • Lamps: run lamp blinks 6×, timer lamp off

Likely causes

Sensor, indoor PCB.

First checks

Measure the sensor's resistance against its R-T table → replace the sensor or the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

Voltage protection (low AC voltage or high DC bus voltage)

Likely causes

Supply, bridge rectifier, IPM board.

First checks

Measure L–N: 220–240 V → check that the DC voltage P–N is in range → check the bridge rectifier → the IPM board → the main board.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 46

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018
  • Indoor unit
  • Lamps: run lamp blinks 6×, timer lamp off

Likely causes

Sensor, its connector, indoor PCB.

First checks

Check the connector; measure the sensor's resistance against its table; sampling voltage below 0.06 V or above 4.94 V = fault → sensor, else PCB.

Source: Oasis Plus 3D Inverter Series 2018 Service Manual, R32, p. 67