Midea error codes

Indoor unit codes

Midea P0

IPM module protection

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi
  • Lamps: run lamp blinks 1×, timer lamp flashing

Likely causes

Supply, wiring, compressor, outdoor fan, bridge rectifier, PFC.

First checks

Measure the DC voltage P–N → check the supply → the wiring between the main board and the IPM → the compressor leads → the IPM → the outdoor fan → the bridge rectifier → the reactor → the PFC → the compressor.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31, 53

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

Compressor top temperature protection

Likely causes

Poor airflow, refrigerant circuit, compressor overload protector (OLP).

First checks

Wait 10 min → is the top of the compressor above 90 °C? → the OLP should read 0 Ω → check the refrigerant circuit → replace the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 54

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018

IPM malfunction or IGBT over-current

  • Outdoor unit
  • Lamps: run lamp blinks 1×, timer lamp flashing

Likely causes

Compressor wiring, IPM, poor ventilation, compressor.

First checks

Check the compressor wiring → IPM continuity → outdoor fan and ventilation → compressor windings → outdoor PCB.

Source: Oasis Plus 3D Inverter Series 2018 Service Manual, R32, p. 70