Midea error codes

Indoor unit codes

Midea P4

Inverter compressor drive error

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi
  • Lamps: run lamp blinks 5×, timer lamp flashing

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 31

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

Discharge temperature protection (above 115 °C)

Likely causes

Low refrigerant charge, discharge sensor.

First checks

Search for a leak and recharge → check the sensor's wiring and resistance → replace the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 51

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018
  • Outdoor unit
  • Lamps: run lamp blinks 5×, timer lamp flashing

Likely causes

Compressor wiring, IPM, poor ventilation, compressor.

First checks

Check the compressor wiring → IPM continuity → outdoor fan and ventilation → compressor windings → outdoor PCB.

Source: Oasis Plus 3D Inverter Series 2018 Service Manual, R32, p. 74

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.

Open in the appAll Midea error codes