Midea error codes

Codes on the indoor display

Midea PC00

IPM module protection or IGBT over-current

Midea – new 4-character codes (current R32 units)

Ranges
  • Oasis Plus
  • All Easy Pro
  • Breezeless E
  • Breezeless+
  • Xtreme Save / Xtreme Save Pro
  • MSAG
  • Solstice
  • Solunar
  • M2OH / M3OE multi
  • Outdoor unit
  • Old Midea code: P0
  • Lamps: run lamp blinks 7×, timer lamp flashing

Likely causes

Compressor wiring, IPM, poor airflow, refrigerant circuit, compressor.

First checks

Check the U / V / W compressor wiring → diode-test the IPM → check the outdoor fan and coil → are the compressor windings balanced? → check the valves and EEV → outdoor PCB, then the compressor.

Source: Midea Service Manual EX R32 3D Inverter, SM_EX(GA)_R32_3D INV_EU_NA1_2510 (Oct 2025), p. 71

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

IPM module protection

Likely causes

Supply, wiring, compressor, outdoor fan, bridge rectifier, PFC.

First checks

Measure the DC voltage P–N → check the supply → the wiring between the main board and the IPM → the compressor leads → the IPM → the outdoor fan → the bridge rectifier → the reactor → the PFC → the compressor.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 53

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.