Mitsubishi Electric error codes
The app finds the right code table from the model number on the nameplate.
Open in the appMitsubishi Electric MSZ-AY / HR / EF / LN – lamp and LED codes
- MSZ-AY / MUZ-AY
- MSZ-HR / MUZ-HR
- MSZ-EF / MUZ-EF
- MSZ-LN / MUZ-LN
How to read codes on this unit
Live indoor blinks: at the first fault after power-on the indoor fan stops and the lamp starts blinking. Outdoor LED on the inverter P.C. board: lit = normal. Otherwise it blinks a number of times, stays off for 2.5 s, and repeats the count.
Switch the power on. On the wireless remote hold Operation select and TEMP ▼ (HR: TOO COOL), press and release RESET, and keep holding for 3 s until all segments of the remote's display show. Point the remote at the unit and press OFF/ON; the unit beeps. Lamp off = the indoor unit is normal. Lamp blinks every 0.5 s with a beep on each blink = indoor fault. If the lamp first stays lit for 3 s without a beep, it is an outdoor fault. For the detailed outdoor recall, set 25 °C on the remote (two beeps) and watch the lamp for at least 1 min, so you see the count at least twice. Always release the recall mode: switch the power off and on, then press RESET on the remote. Clear the fault memory after the repair: start the recall again, press OFF/ON, press E.O. SW on the indoor unit, then release the recall mode as above.
The outdoor manual's recall table also has an outdoor-LED column. It does not match the live LED table (the manual warns about this), so it is not used here: read the outdoor LED with the outdoor LED list. Test run: press E.O. SW once for COOL, twice for HEAT. The unit runs for 30 min at rated frequency (COOL) or 58 Hz (HEAT) with the indoor fan on High.
Indoor lamp, while the fault is live
blinks continuously Miswiring or serial signal error 2 blinks Indoor coil or room thermistor open or short 3 blinks Indoor fan motor fault (no speed feedback) 4 blinks Indoor control system error (nonvolatile memory) 5 blinks Outdoor power system error 6 blinks Outdoor thermistor error 7 blinks Outdoor control system error (nonvolatile memory) 14 blinks or more Other outdoor abnormality lit Outdoor control system error
Indoor lamp in recall mode: indoor faults
1 blink Room thermistor RT11 open or short 2 blinks Indoor coil thermistor error (RT12 main, RT13 sub) 3 blinks Serial signal error 11 blinks Indoor fan motor error 12 blinks Indoor control system error (nonvolatile memory)
Indoor lamp in recall mode: outdoor faults
1 blink Indoor ↔ outdoor communication error (receiving) 2 blinks Outdoor power system error 3 blinks Outdoor thermistor open or short 4 blinks Over-current into power module IC700 detailed recall only4 blinks Compressor synchronous abnormality (start-up failure) detailed recall only5 blinks Discharge temperature too high detailed recall only6 blinks High-pressure protection detailed recall only7 blinks Fin or P.C. board temperature too high detailed recall only8 blinks Outdoor fan motor error detailed recall only9 blinks Outdoor nonvolatile memory error 9 blinks Power module IC700 fault detailed recall only10 blinks Discharge temperature too low detailed recall only11 blinks DC bus voltage or phase current not detected detailed recall only14 blinks Stop valve closed 14 blinks 4-way valve or pipe temperature error 16 blinks Outdoor refrigerant system abnormality
Outdoor inverter-board LED, live
lit Normal 1 blink Outdoor power system, outdoor thermistor or nonvolatile memory error 6 blinks Serial signal error 11 blinks Stop valve closed 14 blinks Other outdoor abnormality 16 blinks 4-way valve or pipe temperature error 17 blinks Outdoor refrigerant system abnormality (closed valve or air in the circuit) 2 blinks Over-current into power module IC700 3 blinks Discharge temperature too high 4 blinks Fin or P.C. board temperature too high 5 blinks High-pressure protection 8 blinks Compressor synchronous abnormality 10 blinks Outdoor fan motor error 12 blinks Phase current not detected 13 blinks DC bus voltage not detected 1 blink Frequency lowered: input current too high (not a fault) unit runs3 blinks Frequency lowered: indoor coil temperature protection unit runs4 blinks Frequency lowered: discharge temperature high unit runs5 blinks Outside-air thermistor open or short (protective operation) unit runs7 blinks Discharge temperature low unit runs8 blinks PAM protection unit runs9 blinks Inverter check mode unit runs