Mitsubishi Electric error codes

Outdoor inverter-board LED, live

Mitsubishi Electric 3 blinks

Frequency lowered: indoor coil temperature protection

Mitsubishi Electric MSZ-AY / HR / EF / LN – lamp and LED codes

Ranges
  • MSZ-AY / MUZ-AY
  • MSZ-HR / MUZ-HR
  • MSZ-EF / MUZ-EF
  • MSZ-LN / MUZ-LN
  • Outdoor unit
  • unit runs

First checks

Check the airflow and the refrigerant charge.

Note

Indoor coil above 55 °C in HEAT, or 8 °C or less in COOL (frost prevention).

Source: Mitsubishi Electric service manual OBH931 Rev B (MUZ-AY, Dec 2024), p. 43

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.

Open in the appAll Mitsubishi Electric error codes