Samsung error codes
C (C101); older documents write the same code with an E (E101). Free Joint Multi outdoor units show their codes on the outdoor board's display.
The app finds the right code table from the model number on the nameplate.
Open in the appSamsung – wall splits (RAC), 3-digit codes
- AR50F / AR60F / AR70F (WindFree)
C101 or E101.
How to read codes on this unit
Indoor display: current models show C + the number, e.g. C101,C554. Older documents and the 2018 service manual write E (E101). It is the same code. Samsung's support page shows the code split in two on the display, e.g.C1 21for C121.E2xx on the indoor unit: an outdoor error is being reported. Read the outdoor code. Outdoor board: the outdoor code shows on the board's 7-segment display and LEDs. Test mode: hold the indoor unit's ON/OFF button for 5 s → forced cooling, turbo fan, anti-freeze protection off. Smart Install (installation check): in standby hold Power + Dry Comfort + Max for 5 s. The display counts 0–99; it takes 7–13 min and ends with a chime or with a code from the installer list.
Installer list (AR50F / AR60F / AR70F installation manual, 2025)
C101 Indoor ↔ outdoor communication error C121 Indoor room temperature sensor error C122 Indoor coil (evaporator) sensor error C123 Indoor coil (evaporator) sensor error C154 Indoor fan motor error C162 Indoor EEPROM error C163 Option code error C422 Refrigerant flow blocked C554 Refrigerant shortage
Full code list (2018 service manual)
E101 = C101.
E101 Indoor ↔ outdoor communication error E102 Indoor ↔ outdoor communication error E121 Indoor room temperature sensor error E122 Evaporator inlet sensor error E123 Evaporator middle sensor error E154 Indoor fan motor error E162 Indoor EEPROM error E163 Option code error E203 Outdoor inverter ↔ main microcontroller communication time-out E221 Outdoor air temperature sensor error E231 Condenser (outdoor coil) sensor error E251 Discharge temperature sensor error E416 Discharge temperature too high E422 EEV or service valve closed (self-diagnosis) E440 Heating blocked: outdoor temperature out of range E441 Cooling blocked: outdoor temperature out of range E458 Outdoor fan motor error E461 Compressor start failure E462 Stop by input current limit E464 IPM over-current E465 Compressor voltage or current limit E466 DC-link voltage too low or too high E467 Compressor wire missing or wrong rotation E468 Current sensor error E469 DC-link voltage sensor error E470 Outdoor EEPROM data error E471 Outdoor EEPROM error (main or inverter microcontroller, OTP) E474 Heatsink temperature sensor error E483 Over-voltage E484 PFC overload E485 Input current sensor error E488 AC input voltage sensor error E500 Heatsink / IPM over-temperature E554 Refrigerant leak
Samsung – Free Joint Multi outdoor units (AJ…TXJ…KG)
- Free Joint Multi (FJM)
How to read codes on this unit
The code shows on the two-digit segment displays of the outdoor main PCB (MAIN-OUT). At first power-up the display shows E199 and the number of indoor units until the pipe check has been run. Press K1 once to run it (3–5 min). K1 presses: 1 = pipe check, 2 = cooling test run, 3 = heating test run, 4 = pump-down, 5 = end. K3 = reset. K4 = view mode. Each press shows the next item: compressor Hz, target Hz, EEV 0–4, fan rpm, discharge temperature, OLP temperature, condenser temperature, outdoor temperature, current, target discharge temperature, total indoor capacity, safety state. The indoor units report the Samsung indoor codes (E101, E121, E122, E123, E154, E162, E163) on their display or LEDs. A wired controller shows them via its Test button.
Outdoor unit codes
E108 Duplicate address: two or more devices have the same address E190 Pipe check error E199 Pipe check not yet done E201 Indoor ↔ outdoor communication error E202 Communication error with all indoor units, or outdoor communication cable E203 Inverter PCB ↔ main PCB communication error E221 Outdoor ambient sensor error E237 Condenser sensor error E251 Discharge temperature sensor error E320 Compressor OLP sensor error E330 Room A pipe-in sensor error E331 Room B pipe-in sensor error E332 Room C pipe-in sensor error E333 Room D pipe-in sensor error E335 Room A pipe-out sensor error E336 Room B pipe-out sensor error E337 Room C pipe-out sensor error E338 Room D pipe-out sensor error E401 Stopped by freeze protection E404 Stopped by overload protection E416 Stopped by high discharge temperature E422 High-pressure blockage control E440 Heating restricted: outdoor temperature out of range E441 Cooling restricted: outdoor temperature out of range E458 Outdoor fan motor error E461 Compressor operation failure E462 Stopped by full-load current control E463 Stopped by OLP temperature E464 Compressor over-current E465 Compressor voltage limit E466 DC-link voltage too low or too high E467 Abnormal compressor speed or compressor wire not connected E468 Output current sensor error E469 DC-link voltage sensor error E470 Outdoor EEPROM read / write error E471 Outdoor EEPROM read / write error (OTP) E474 IPM / PFCM temperature sensor error E483 DC-link over-voltage (hardware detection) E484 PFC overload (over-current) E485 Input current sensor error E488 Supply voltage sensor error E500 IPM / PFCM overheat E507 High-pressure switch open or stop by high pressure E554 Refrigerant completely lost from the outdoor unit E563 Incompatible indoor unit software E590 Inverter EEPROM checksum error
No codes yet for: AR40H