Calculators that know the refrigerant and the altitude.

9 calculators for refrigerant, installation and electrics. Set the refrigerant, pressure unit, altitude and gauge zero once: they apply to every calculator that needs them.

Open the calculators

No account needed.

Superheat and subcooling, judged.

Enter a pressure and a pipe temperature and get the result in a word too: normal, high or low.

  • For blends: the dew point for superheat, the bubble point for subcooling.
  • Subcooling from the high-side pressure or from a temperature measured on the coil.
  • The result shows the formula and which operation the limits are for.

Pressure ↔ temperature for 11 refrigerants.

Saturation pressure at a temperature, or the evaporating and condensing temperature at a pressure, with a P-T chart.

  • R32 at 9.00 bar g at sea level → 6.7 °C.
  • For blends both curves, vapour side and liquid side, and the temperature glide.
  • Pressure in bar g, bar abs, psig or MPa g; tables from CoolProp 8.0.0.

Vacuum test: holds, moisture or a leak?

From the readings after closing the pump off it tells you whether the system is tight and dry, with the makers’ rules too (Midea, Mitsubishi, Samsung, Daikin).

  • On a manifold in bar g or on a micron gauge in µm.
  • A rise that slows down is moisture; a steady rise is a leak.
  • Vacuum depth on a manifold is judged for the site’s altitude.