Diagnose: from the symptom to the likely cause.
Unit, symptoms, error codes, checks and readings in one place. It compares each reading with the normal range and tells you what to check first.
A free sign-in is enough.
During the beta, Pro is free for everyone who signs in.
DiagnoseSymptoms and checks
Symptoms
Not cooling / heating enoughRoom stays warm, weak or lukewarm airStops after a whileRuns, then cuts out or goes quietIce on indoor coil or pipesFrost on the coil or the thick pipe
Checks for “Not cooling / heating enough”
- Is the indoor filter clean?CleanDirty
- Are both service valves fully open, with their caps on?Fully openClosed / part-open
CalculatorsError codesDiagnoseStart-upMore
DiagnoseResult
Readings
- Superheat6.8 Knormal 0–5 K
high - Subcooling1.2 Knormal 2.5–10 K
low - Evaporating2.5 °Cnormal 2–13 °C
normal
Likely causes Pro
1Low charge / leakLikely · Subcooling 1.2 K: low
CalculatorsError codesDiagnoseStart-upMore
Start with what you see.
Tick the symptoms and add the error code if one is showing. Each symptom brings its checks: cheapest and likeliest first.
- Symptoms in a technician’s words, from “not cooling enough” to a tripping breaker.
- Finds the error code in the code library for the unit’s maker.
- On-site checks: settings, filter, coils, valves, power.
DiagnoseSymptoms and checks
Symptoms
Not cooling / heating enoughRoom stays warm, weak or lukewarm airStops after a whileRuns, then cuts out or goes quietIce on indoor coil or pipesFrost on the coil or the thick pipe
Checks for “Not cooling / heating enough”
- Is the indoor filter clean?CleanDirty
- Are both service valves fully open, with their caps on?Fully openClosed / part-open
CalculatorsError codesDiagnoseStart-upMore
Readings checked against normal.
Superheat, subcooling, evaporating and discharge temperature, current and compressor insulation: each with its normal range and a word, normal, high or low.
- How to start the test run, per maker: pressures are judged with the compressor at a steady speed.
- What the checks found is in the result, with the fix.
- Ranked likely causes, repair guides and maker charts.
Pro
DiagnoseResult
Readings
- Superheat6.8 Knormal 0–5 K
high - Subcooling1.2 Knormal 2.5–10 K
low - Evaporating2.5 °Cnormal 2–13 °C
normal
Likely causes Pro
1Low charge / leakLikely · Subcooling 1.2 K: low
CalculatorsError codesDiagnoseStart-upMore
Save the result to the unit.
The diagnosis goes into the unit’s history with today’s date. On the next visit you see what was found last time.
- Symptoms, error codes, readings with their verdict and what was found on site.
- A unit you don’t have yet can be added while saving.
- The diagnosis itself holds technical data only; the customer, if any, is on the unit.
Units and F-gasHistory
Midea Oasis 3.5 kWB-01R32 · 0.85 kg · 0.57 t CO₂-eq
History
- 12 Nov 2026 · DiagnosisCooling · R32Symptoms: Not cooling / heating enough
- Superheat6.8 K
high - Subcooling1.2 K