Error codes by brand

Midea error codes

Midea uses two code systems. Units from about 2017–2019 show a 2-character code (E1, P4); current units show a 4-character code (EL01, PC04). The same fault has a different code in each system. If you don't know which one your unit has, look at the display: 2 or 4 characters?

Midea – new 4-character codes (current R32 units)

Ranges
  • Oasis Plus
  • All Easy Pro
  • Breezeless E
  • Breezeless+
  • Xtreme Save / Xtreme Save Pro
  • MSAG
  • Solstice
  • Solunar
  • M2OH / M3OE multi

The current Midea code system with 4-character codes (EH00, EL01, PC04 …), from Midea's EX R32 service manual (2025) and Midea's 2019 slides on the new code system. Use it for current Midea R32 splits (Oasis Plus, All Easy Pro, Breezeless, Xtreme Save, Solstice, Solunar, M2OH / M3OE indoor units) and Midea-built Vivax units whose display shows 4 characters (AERI / AEMI / AEQI PRO, COFM multi).

How to read codes on this unit
  • The indoor display shows the 4-character code, sometimes with a gap (EL 01). 1st letter: E error, P protection, F fault, L frequency limit. 2nd letter: H indoor, C outdoor, L other.
  • Units without a display flash the lamps instead: the run lamp flashes (2 Hz) a number of times, and the timer lamp is off, on or flashing. Some codes share one pattern (EH60 and EH61; EC51 to EC54): for those, read the display or engineering mode.
  • Not errors: F or dF defrost · CL active clean · FP 8 °C heating · FC forced cooling · AP Wi-Fi AP mode · CP switched off by the remote.
  • Engineering mode (remote RG10E27): hold POWER + FAN for 7 s (the remote shows 0); ▲ / ▼ picks a channel. Exit with POWER + FAN for 2 s, or wait 60 s.
  • Channels: 0 current error code, 1 T1, 2 T2, 3 T3, 4 T4, 5 TP, 6 target Hz, 7 actual Hz, 8 current, 9 AC volts ÷ 10 … Not confirmed: this channel list comes from the manual's text and was not checked against the printed page.
  • Older remotes: use the information inquiry instead: within 10 s press LED ×3, then SWING ×3. Items: T1, T2, T3, T4, Tb, TP, TH, FT, Fr, IF, OF, LA, CT, ST.
  • Garbled or unknown code: first make sure it is not a temperature. If the unit ignores the remote → indoor PCB; if it obeys → display board.
  • Many codes have an old 2-character equivalent on older Midea units (e.g. EL01 = E1). The old compressor-drive sub-codes P40 … P49 are PC40 … PC49 here.

Codes on the indoor display

Lamp patterns are from Midea's 2019 slides on the new code system. The slides give the same pattern to several codes (EH60 and EH61; EC51 to EC54), so those patterns are not confirmed.

Extended list (engineering mode)

Shown in engineering mode on channel 0, or on units that display them.

Frequency limits (not faults)

The unit limits the compressor frequency; the code says what causes the limit.

  • LH00 Frequency limited by indoor coil temperature T2
  • LH30 Frequency limited by indoor fan current
  • LH31 Frequency limited by indoor fan voltage
  • LH07 Frequency limited by the remote control
  • LC01 Frequency limited by outdoor coil temperature T3
  • LC02 Frequency limited by discharge temperature TP
  • LC03 Frequency limited by current
  • LC05 Frequency limited by voltage
  • LC06 Frequency limited by IPM temperature
  • LC30 Frequency limited by high pressure
  • LC31 Frequency limited by low pressure

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

Codes from the Inventor multi split service manual for the U6RSL(2)-18, U6RSL(3)-27 and U6RSL(5)-42 outdoor units and the indoor units connected to them. The 2-port (2)-18 shows 2-character codes on its outdoor display; the (3)-27 and (5)-42 show 4-character codes for the same faults.

How to read codes on this unit
  • Indoor units show the indoor codes on their display. Units without a display flash the lamps instead: the operation lamp blinks a number of times, and the timer lamp is off, on or flashing (2 Hz).
  • Outdoor 7-segment display: -- = standby; a number = running frequency in Hz; dF = defrost; PH = pre-heat; RO = oil return; LC = low-ambient cooling; FC = forced cooling; E6 = 3 PFC trips within 15 min; CE = auto-correction running. Anything else is an error code.
  • Outdoor codes clear at least 30 s after the fault has gone, except E2 and E3 on the (2)-18.
  • Point check (SW1): press SW1 repeatedly while the unit runs to step through the readings. On the (3)-27, press 49 shows why the unit stopped; on the others, press 45 shows the last error code (00 = none) and press 52 the reason for the last shutdown.
  • Wiring / piping auto-correction: hold the outdoor check switch for 5 s until CE shows; it takes 5–10 min.
  • The U5MRSL (4-port) and the Midea M2OH / M3OE outdoor units are covered only by inference from this manual: the U5MRSL is the same Inventor multi range without its own service manual; for the M2OH / M3OE the hints are the shared GMCC compressor and the Midea outdoor model names in this manual. Check the 7-segment display on the unit before relying on this table for them.

Indoor unit codes

Shown on the display or by the lamps of the indoor units connected to the multi.

Outdoor display codes: U6RSL(2)-18

The 2-character codes on the 7-segment display of the 2-port outdoor unit.

Outdoor display codes: U6RSL(3)-27 and U6RSL(5)-42

The 4-character codes on the 7-segment display of the 3-port and 5-port outdoor units.

Midea – old 2-character codes (about 2017–2019)

Ranges
  • Oasis Plus 2018

The old Midea code system with 2-character codes, from the Oasis Plus 2018 service manual (Midea units also sold under other names, e.g. Carrier 42QHP / 38QHP). Use it for Midea-built units of about 2017–2019 whose display shows 2 characters, e.g. Vivax AEYIs.

How to read codes on this unit
  • The indoor display shows the 2-character code. Units without a display flash the lamps instead: the run lamp blinks a number of times, and the timer lamp is off, on or flashing.
  • Information inquiry (live readings): within 10 s press LED ×3, then SWING ×3; a 2 s beep confirms. LED shows the next item, SWING the previous one. Each item's name shows for 2 s, then its value for 25 s.
  • Items: T1, T2, T3, T4, TP, FT (target Hz), Fr (actual Hz, printed TR), dL (current), Uo (AC volts), Sn (capacity test), -- (running mode), Pr (outdoor fan), Lr (EXV), Ir (indoor fan), HU, TT, dT, IF (Wi-Fi), oT.
  • Each code has a new 4-character equivalent on current Midea units (e.g. E1 = EL01).

Codes in the 2018 service manual

Lamp patterns are from Midea's 2019 code-system slides, which use the same old system.

Codes added in Midea's 2019 list of the old system

Not on the 2018 unit's list, but part of the same old system in Midea's 2019 slides.