Midea error codes
E1, P4); current units show a 4-character code (EL01, PC04). The same fault has a different code in each system. If you don't know which one your unit has, look at the display: 2 or 4 characters?
The app finds the right code table from the model number on the nameplate.
Open in the appMidea – new 4-character codes (current R32 units)
- Oasis Plus
- All Easy Pro
- Breezeless E
- Breezeless+
- Xtreme Save / Xtreme Save Pro
- MSAG
- Solstice
- Solunar
- M2OH / M3OE multi
EH00, EL01, PC04 …), from Midea's EX R32 service manual (2025) and Midea's 2019 slides on the new code system. Use it for current Midea R32 splits (Oasis Plus, All Easy Pro, Breezeless, Xtreme Save, Solstice, Solunar, M2OH / M3OE indoor units) and Midea-built Vivax units whose display shows 4 characters (AERI / AEMI / AEQI PRO, COFM multi).
How to read codes on this unit
The indoor display shows the 4-character code, sometimes with a gap ( EL 01). 1st letter: E error, P protection, F fault, L frequency limit. 2nd letter: H indoor, C outdoor, L other.Units without a display flash the lamps instead: the run lamp flashes (2 Hz) a number of times, and the timer lamp is off, on or flashing. Some codes share one pattern ( EH60andEH61;EC51toEC54): for those, read the display or engineering mode.Not errors: FordFdefrost ·CLactive clean ·FP8 °C heating ·FCforced cooling ·APWi-Fi AP mode ·CPswitched off by the remote.Engineering mode (remote RG10E27): hold POWER + FAN for 7 s (the remote shows 0); ▲ / ▼ picks a channel. Exit with POWER + FAN for 2 s, or wait 60 s.Channels: 0 current error code, 1 T1, 2 T2, 3 T3, 4 T4, 5 TP, 6 target Hz, 7 actual Hz, 8 current, 9 AC volts ÷ 10 … Not confirmed: this channel list comes from the manual's text and was not checked against the printed page. Older remotes: use the information inquiry instead: within 10 s press LED ×3, then SWING ×3. Items: T1, T2, T3, T4, Tb, TP, TH, FT, Fr, IF, OF, LA, CT, ST. Garbled or unknown code: first make sure it is not a temperature. If the unit ignores the remote → indoor PCB; if it obeys → display board. Many codes have an old 2-character equivalent on older Midea units (e.g. EL01=E1). The old compressor-drive sub-codesP40…P49arePC40…PC49here.
Codes on the indoor display
EH60 and EH61; EC51 to EC54), so those patterns are not confirmed.
EH00 Indoor EEPROM malfunction EH0A Indoor EEPROM parameter error EL01 Indoor ↔ outdoor communication error EH02 Zero-crossing detection error EH03 Indoor fan speed out of control EH60 Room sensor T1 open or short EH61 Indoor coil sensor T2 open or short EH0b Indoor PCB ↔ display board communication error EL0C Refrigerant shortage detected (leak detection) EC51 Outdoor EEPROM parameter error EC52 Outdoor coil sensor T3 open or short EC53 Outdoor ambient sensor T4 open or short EC54 Discharge sensor TP open or short EC56 Indoor coil outlet sensor T2B open or short (multi split) EC07 Outdoor fan speed out of control PC00 IPM module protection or IGBT over-current PC01 Over- or under-voltage (DC bus P–N out of range) PC02 Compressor top or IPM over-temperature PC03 High or low pressure protection (units with pressure switches) PC04 Inverter compressor drive error PC08 Over-current protection -- Indoor units in conflicting modes (multi split) FH0P Wi-Fi AP mode active, but no Wi-Fi module fitted
Extended list (engineering mode)
EH30 Indoor external fan parameter error EH35 Indoor external fan phase loss EH36 Indoor external fan current-sampling bias EH37 Indoor external fan zero speed EH38 Indoor external fan stall EH39 Indoor external fan out of step EH3A Indoor external fan DC bus voltage low EH3E Indoor external fan over-current EH3F Indoor external fan hardware over-current EC55 Outdoor IPM temperature sensor (TH) fault EC71 Outdoor fan over-current EC72 Outdoor fan phase loss EC73 Outdoor fan zero speed EC74 Outdoor fan current-sampling bias EC75 Outdoor fan hardware over-current PC10 Outdoor AC voltage too low PC11 Outdoor DC bus voltage too high PC12 Outdoor DC bus voltage too low PC40 Main chip ↔ driver chip communication error PC41 Compressor current-sampling circuit fault PC42 Compressor start failure PC43 Compressor phase loss PC44 Compressor zero-speed protection PC45 Voltage drop (compressor loses power) PC46 Compressor speed out of control PC49 Compressor over-current PC06 Discharge pipe high temperature PC0F PFC failure PC30 High pressure protection PC31 Low pressure protection PC0L Low outdoor temperature protection PC0A Condenser high temperature PH09 Anti-cold-air in heating PH0c Humidity sensor fault PH90 Evaporator high temperature protection PH91 Evaporator low temperature protection
Frequency limits (not faults)
LH00 Frequency limited by indoor coil temperature T2 LH30 Frequency limited by indoor fan current LH31 Frequency limited by indoor fan voltage LH07 Frequency limited by the remote control LC01 Frequency limited by outdoor coil temperature T3 LC02 Frequency limited by discharge temperature TP LC03 Frequency limited by current LC05 Frequency limited by voltage LC06 Frequency limited by IPM temperature LC30 Frequency limited by high pressure LC31 Frequency limited by low pressure
Inventor U6RSL multi split (Midea-built)
- M2OH / M3OE multi
How to read codes on this unit
Indoor units show the indoor codes on their display. Units without a display flash the lamps instead: the operation lamp blinks a number of times, and the timer lamp is off, on or flashing (2 Hz). Outdoor 7-segment display: --= standby; a number = running frequency in Hz;dF= defrost;PH= pre-heat;RO= oil return;LC= low-ambient cooling;FC= forced cooling;E6= 3 PFC trips within 15 min;CE= auto-correction running. Anything else is an error code.Outdoor codes clear at least 30 s after the fault has gone, except E2andE3on the (2)-18.Point check (SW1): press SW1 repeatedly while the unit runs to step through the readings. On the (3)-27, press 49 shows why the unit stopped; on the others, press 45 shows the last error code ( 00= none) and press 52 the reason for the last shutdown.Wiring / piping auto-correction: hold the outdoor check switch for 5 s until CEshows; it takes 5–10 min.The U5MRSL (4-port) and the Midea M2OH / M3OE outdoor units are covered only by inference from this manual: the U5MRSL is the same Inventor multi range without its own service manual; for the M2OH / M3OE the hints are the shared GMCC compressor and the Midea outdoor model names in this manual. Check the 7-segment display on the unit before relying on this table for them.
Indoor unit codes
E0 Indoor EEPROM error E1 Indoor ↔ outdoor communication error E3 Indoor fan speed out of range E4 Room sensor T1 open or short E5 Indoor coil sensor T2 open or short EC Refrigerant leak detected EE Water-level alarm F0 Over-current protection F1 Outdoor ambient sensor T4 open or short F2 Outdoor coil sensor T3 open or short F3 Discharge sensor T5 open or short F4 Outdoor EEPROM error F5 Outdoor fan speed out of range F6 Pipe sensor T2B open or short FA Communication error between the two chips on the indoor PCB P0 IPM module protection P1 Over- or under-voltage protection P3 Ambient temperature too low P4 Inverter compressor drive error -- Indoor units in conflicting modes P6 Low-pressure protection
Outdoor display codes: U6RSL(2)-18
E0 Outdoor EEPROM error E2 Indoor ↔ outdoor communication error E3 IPM board ↔ main board communication error E4 Outdoor sensor T3, T4 or T5 open or short F1 T2B sensor of room A missing or faulty F2 T2B sensor of room B missing or faulty F3 T2B sensor of room C missing or faulty F4 T2B sensor of room D missing or faulty F5 T2B sensor of room E missing or faulty E5 Voltage protection (low AC voltage or high DC bus voltage) E6 PFC protection E8 Outdoor fan speed or compressor speed error P0 Compressor top temperature protection P3 Compressor current protection P4 Discharge temperature protection (above 115 °C) P5 Condenser high-temperature protection (T3 above 65 °C) P6 IPM module protection E9 Wiring error with a 24k indoor unit LP Low outdoor ambient protection
Outdoor display codes: U6RSL(3)-27 and U6RSL(5)-42
EC51 Outdoor EEPROM error EL01 Indoor ↔ outdoor communication error PC40 IPM board ↔ main board communication error EC50 Outdoor sensor T3, T4 or T5 open or short EC52 Outdoor coil sensor T3 open or short EC53 Outdoor ambient sensor T4 open or short EC54 Discharge sensor T5 open or short EC56 T2B sensor of one room missing or faulty PC10 Low AC voltage protection PC11 High DC bus voltage protection PC12 High DC bus voltage or 341 MCE error PC0F PFC protection EC07 Outdoor fan speed out of range EC71 Outdoor fan over-current EC72 Outdoor fan phase loss PC02 Compressor top temperature protection PC08 Compressor current protection PC44 Compressor zero speed PC46 Compressor speed out of control PC49 Compressor over-current PC43 Compressor phase loss PC45 IR drive chip failure PC06 Discharge temperature protection (above 115 °C) PC0A Condenser high-temperature protection (T3 above 65 °C) PC00 IPM module protection PC30 High-pressure protection PC31 Low-pressure protection PC0L Low outdoor ambient protection
Midea – old 2-character codes (about 2017–2019)
- Oasis Plus 2018
How to read codes on this unit
The indoor display shows the 2-character code. Units without a display flash the lamps instead: the run lamp blinks a number of times, and the timer lamp is off, on or flashing. Information inquiry (live readings): within 10 s press LED ×3, then SWING ×3; a 2 s beep confirms. LED shows the next item, SWING the previous one. Each item's name shows for 2 s, then its value for 25 s. Items: T1, T2, T3, T4, TP, FT (target Hz), Fr (actual Hz, printed TR), dL (current), Uo (AC volts), Sn (capacity test),--(running mode), Pr (outdoor fan), Lr (EXV), Ir (indoor fan), HU, TT, dT, IF (Wi-Fi), oT.Each code has a new 4-character equivalent on current Midea units (e.g. E1=EL01).
Codes in the 2018 service manual
E0 Indoor EEPROM parameter error E1 Indoor ↔ outdoor communication error E3 Indoor fan speed out of range E4 Room sensor T1 open or short E5 Indoor coil sensor T2 open or short Eb Indoor PCB ↔ display board communication error EF Intelligent-eye module error F0 Overload current protection F1 Outdoor ambient sensor T4 open or short F2 Outdoor coil sensor T3 open or short F3 Discharge sensor TP open or short F4 Outdoor EEPROM parameter error F5 Outdoor fan speed out of range P0 IPM malfunction or IGBT over-current P1 Over- or under-voltage P2 IPM high temperature P4 Inverter compressor drive error