Midea error codes

Outdoor display codes: U6RSL(3)-27 and U6RSL(5)-42

Midea EC50

Outdoor sensor T3, T4 or T5 open or short

Inventor U6RSL multi split (Midea-built)

Ranges
  • M2OH / M3OE multi

Likely causes

Sensor, its connector, outdoor PCB.

First checks

Check the connector → measure the sensor's resistance against its R-T table (T5: 5 kΩ at 90 °C) → replace the sensor or the PCB.

Source: Inventor Multi Split Unit Service Manual V:1.0.062022, p. 33–34

In the app you also find codes by the model number on the nameplate, and Diagnose judges your readings.