Error codes by brand

Vivax error codes

Most Vivax ranges are built on Midea platforms (Midea remotes and Midea texts in the manuals): they use Midea's codes, old or new depending on the range. The T Design (LCTI) range comes from a different maker and has its own short code list, without service data.

Midea – new 4-character codes (current R32 units)

Ranges
  • AERI PRO / AEMI PRO / AEQI PRO / AEGI PRO / AEXI PRO / AEFI PRO
  • AENI (N+)
  • AEHI+ (H+)
  • COFM multi

The current Midea code system with 4-character codes (EH00, EL01, PC04 …), from Midea's EX R32 service manual (2025) and Midea's 2019 slides on the new code system. Use it for current Midea R32 splits (Oasis Plus, All Easy Pro, Breezeless, Xtreme Save, Solstice, Solunar, M2OH / M3OE indoor units) and Midea-built Vivax units whose display shows 4 characters (AERI / AEMI / AEQI PRO, COFM multi).

How to read codes on this unit
  • The indoor display shows the 4-character code, sometimes with a gap (EL 01). 1st letter: E error, P protection, F fault, L frequency limit. 2nd letter: H indoor, C outdoor, L other.
  • Units without a display flash the lamps instead: the run lamp flashes (2 Hz) a number of times, and the timer lamp is off, on or flashing. Some codes share one pattern (EH60 and EH61; EC51 to EC54): for those, read the display or engineering mode.
  • Not errors: F or dF defrost · CL active clean · FP 8 °C heating · FC forced cooling · AP Wi-Fi AP mode · CP switched off by the remote.
  • Engineering mode (remote RG10E27): hold POWER + FAN for 7 s (the remote shows 0); ▲ / ▼ picks a channel. Exit with POWER + FAN for 2 s, or wait 60 s.
  • Channels: 0 current error code, 1 T1, 2 T2, 3 T3, 4 T4, 5 TP, 6 target Hz, 7 actual Hz, 8 current, 9 AC volts ÷ 10 … Not confirmed: this channel list comes from the manual's text and was not checked against the printed page.
  • Older remotes: use the information inquiry instead: within 10 s press LED ×3, then SWING ×3. Items: T1, T2, T3, T4, Tb, TP, TH, FT, Fr, IF, OF, LA, CT, ST.
  • Garbled or unknown code: first make sure it is not a temperature. If the unit ignores the remote → indoor PCB; if it obeys → display board.
  • Many codes have an old 2-character equivalent on older Midea units (e.g. EL01 = E1). The old compressor-drive sub-codes P40 … P49 are PC40 … PC49 here.

Codes on the indoor display

Lamp patterns are from Midea's 2019 slides on the new code system. The slides give the same pattern to several codes (EH60 and EH61; EC51 to EC54), so those patterns are not confirmed.

Extended list (engineering mode)

Shown in engineering mode on channel 0, or on units that display them.

  • EH30 Indoor external fan parameter error
  • EH35 Indoor external fan phase loss
  • EH36 Indoor external fan current-sampling bias
  • EH37 Indoor external fan zero speed
  • EH38 Indoor external fan stall
  • EH39 Indoor external fan out of step
  • EH3A Indoor external fan DC bus voltage low
  • EH3E Indoor external fan over-current
  • EH3F Indoor external fan hardware over-current
  • EC55 Outdoor IPM temperature sensor (TH) fault
  • EC71 Outdoor fan over-current
  • EC72 Outdoor fan phase loss
  • EC73 Outdoor fan zero speed
  • EC74 Outdoor fan current-sampling bias
  • EC75 Outdoor fan hardware over-current
  • PC10 Outdoor AC voltage too low
  • PC11 Outdoor DC bus voltage too high
  • PC12 Outdoor DC bus voltage too low
  • PC40 Main chip ↔ driver chip communication error
  • PC41 Compressor current-sampling circuit fault
  • PC42 Compressor start failure
  • PC43 Compressor phase loss
  • PC44 Compressor zero-speed protection
  • PC45 Voltage drop (compressor loses power)
  • PC46 Compressor speed out of control
  • PC49 Compressor over-current
  • PC06 Discharge pipe high temperature
  • PC0F PFC failure
  • PC30 High pressure protection
  • PC31 Low pressure protection
  • PC0L Low outdoor temperature protection
  • PC0A Condenser high temperature
  • PH09 Anti-cold-air in heating
  • PH0c Humidity sensor fault
  • PH90 Evaporator high temperature protection
  • PH91 Evaporator low temperature protection

Frequency limits (not faults)

The unit limits the compressor frequency; the code says what causes the limit.

  • LH00 Frequency limited by indoor coil temperature T2
  • LH30 Frequency limited by indoor fan current
  • LH31 Frequency limited by indoor fan voltage
  • LH07 Frequency limited by the remote control
  • LC01 Frequency limited by outdoor coil temperature T3
  • LC02 Frequency limited by discharge temperature TP
  • LC03 Frequency limited by current
  • LC05 Frequency limited by voltage
  • LC06 Frequency limited by IPM temperature
  • LC30 Frequency limited by high pressure
  • LC31 Frequency limited by low pressure

Midea – old 2-character codes (about 2017–2019)

Ranges
  • AENI (N+)
  • AEHI+ (H+)
  • AEYIs (Y)

The old Midea code system with 2-character codes, from the Oasis Plus 2018 service manual (Midea units also sold under other names, e.g. Carrier 42QHP / 38QHP). Use it for Midea-built units of about 2017–2019 whose display shows 2 characters, e.g. Vivax AEYIs.

How to read codes on this unit
  • The indoor display shows the 2-character code. Units without a display flash the lamps instead: the run lamp blinks a number of times, and the timer lamp is off, on or flashing.
  • Information inquiry (live readings): within 10 s press LED ×3, then SWING ×3; a 2 s beep confirms. LED shows the next item, SWING the previous one. Each item's name shows for 2 s, then its value for 25 s.
  • Items: T1, T2, T3, T4, TP, FT (target Hz), Fr (actual Hz, printed TR), dL (current), Uo (AC volts), Sn (capacity test), -- (running mode), Pr (outdoor fan), Lr (EXV), Ir (indoor fan), HU, TT, dT, IF (Wi-Fi), oT.
  • Each code has a new 4-character equivalent on current Midea units (e.g. E1 = EL01).

Codes in the 2018 service manual

Lamp patterns are from Midea's 2019 code-system slides, which use the same old system.

Codes added in Midea's 2019 list of the old system

Not on the 2018 unit's list, but part of the same old system in Midea's 2019 slides.

Vivax T Design (ACP-…LCTI)

Ranges
  • T Design

Codes from the owner's manual of the Vivax T Design (ACP-12CH35LCTI, ACP-18CH50LCTI). This range is not Midea-built and no service manual was found, so the codes have only their meanings: the maker publishes no causes or checks.

How to read codes on this unit
  • The indoor display shows the code. The owner's manual has no lamp table and no self-diagnosis mode.
  • These codes are not the Midea ones: here E1 is the room sensor, not communication.
  • The manual button on the indoor unit starts forced operation, meant for testing and emergencies.

Display codes

The owner's manual gives meanings only: no causes or checks are published for these codes.